Error code

Inverter larm (0) Inverter alarm and compressor overload

Fault

ComfortZone · EX

Applies to 3 models
EX35, EX50, EX65

What this means

The inverter alarm indicates possible compressor overload, compressor or inverter failure, or an interrupted alarm circuit. On new installations, air in the system, poor water circulation, or an undersized radiator system are common causes. The circulation-water return temperature must not exceed 55 °C and hot-water temperature must not exceed 60 °C.

When to call a technician